Secop Compressors FAQ – AC-Powered

Find our answers to the most frequently asked questions on AC-Powered topics.

What determines the noise level of a cooling system?

The most relevant factors are:

  • Combination of components in the cooling system (layout and installation)
  • Pulsations and turbulences in the refrigerant gas related to the specific system
  • Actual level of system insulation
  • Function of machine compartment
  • Actual system vibration prevention
  • Suction and/or pressure mufflers 
There are no data sheets for R12 or R22 compressor in the data sheet selector.

We don't have the data sheets of our older compressor and condensing unit types on our website, but we will gladly send you the documentation by mail or e-mail on request.

What is the function of a PTC?

The PTC protects the start winding by switching it off.

When can a PTC be used?

A compressor can be started using a PTC if the appliance has a standstill period of a minimum period of seven minutes in order to ensure pressure equalization via the capillary tube.

Will the wiring in the compressor automatically fail when the PTC starting device burns out? Can the compressor be ohmed out to check for shortings?

Generally, the compressor should be still okay even if the PTC starting device burns out – we recommend using a new PTC instead.

The nominal values for the main winding and for the start winding at a temperature of 25°C are stated in the data sheet. Depending on the actual ambient temperature, this nominal value has to be corrected by a factor from the following table.

t/°C

t/°F

Factor

10

50

0.942

15

59

0.961

20

68

0.981

25

77

1.000

30

86

1.019

35

95

1.039

40

104

1.058

45

113

1.077

50

122

1.096

Example: For the NL7CNK compressor, the value given in the data sheet is 14.7 Ohm @ 25°C. If your ambient temperature is 40°C, you have to multiply this by 1.058 as declared in the table. So your resistance would be 1.058 x 14.7 Ohm = 15.6 Ohm. Please note that these values apply only if the resistance is measured directly at the stator – you should include a tolerance of about +/- 10%.

What is the advantage of an ePTC?

The main advantage of the ePTC solution is the easy way of saving energy in existing and future fridge and freezer designs.

This is due to the following factors:

  • Reduction of 2 W in power consumption
  • Full PTC protection of start winding
  • Can be operated with a run capacitor
  • Silent operation
  • Short recovery time
  • Compatibility to all Secop 103N PTC starters

 In special cases, an ePTC can replace a PTC/run capacitor combination.

What does the stamping on a capacitor mean, for example, AC 220V 1.7% ED SD = 3MIN AC 280V 0.55% ED SD = 1MIN

In this example, the capacitor can operate at 220 V AC for a maximum time of 1.7% within three minutes. More exactly, this means the capacitor should be operated for a maximum of 3.1 seconds and afterwards be turned off for 176.9 seconds. At 280 V AC, the capacitor can be used for 0.3 seconds in a period of one minute.

Can capacitors with a different rating than specified in your literature be used?

Yes, that is possible. The voltage rating of all capacitors must be the same as, or higher than, the specified voltage.

Can I replace the standard run capacitor delivered by Secop with another type having the same electrical data but with safety class P0?

For safety reasons, Secop only distributes run capacitors of safety class P2 (with aluminum housing) instead of safety class P0 (with plastic housing) with its compressors. A P0 run capacitor is normally not used by, for example, German manufacturers because of safety and insurance reasons.

On the other hand, we know that P0 run capacitors are used by several manufacturers elsewhere. If a P0 run capacitor is used, it is very important to follow the instructions from the supplier regarding safety conception to prevent any fire in case the flammable capacitor, which is not protected, fails – for example, the distance to flammable parts should be at least 100 mm or the capacitor should be encapsulated.

So when technical matters are ok on the P0 capacitor we cannot see why it should not be operated with a Secop compressor. Also, please consider that the Secop run capacitor holder probably will not fit the capacitor. Compact installation including earth connection cannot be ensured because it cannot be installed directly on the compressing housing.

Can existing starting equipment be used with another compressor?

Generally no, it cannot.

The Secop Engineering department has selected optimized starting equipment for each compressor which meets the requirements and specifications. We, therefore, strongly advise using only the starting equipment that is recommended by Secop.

Especially when using starting relays, the cut-in and cutout current values have to match the motor requirements precisely. A wrong relay can destroy the motor or the start capacitor and cause severe safety problems.

Does the designation "198 V to 254 V" state the start voltage range or the working voltage range?

When we state a voltage range of 198 V to 254 V in our catalogs, it means that the compressor can both run and start at voltages within this range.

Can Secop recommend substitutes for failing compressors in old appliances?

Example: A cooler from 1977 is equipped with a PW7.5K14 compressor. For several months, the compressor ran longer and longer and finally worked continuously. Since the thermostat is operational, it is probable that the compressor has reached the end of its lifecycle. Is there any appropriate substitute?

No, Secop will does not recommend substitutes for failing old devices. If a compressor that has been used in an appliance for ten or more years finally fails, replacing the compressor is not recommended, even if it is technically feasible. After ten or more years of use, the insulation and the sealing of a refrigerator and freezer are used up. This would lead to significantly increased energy consumption.

Furthermore, the refrigerant R12 is no longer allowed in most countries. Replacing it with another refrigerant will become quite expensive.

The sensible recommendation is to buy a new appliance.

What is the recommended position to transport a refrigerator horizontally over a short distance?

The positions in which each compressor is allowed to be shipped are stated in the Product Bulletin – Shipment of Refrigeration Appliances in the Horizontal Position. If the unit has been shipped in the correct position in accordance with the Technical Information, we recommend waiting 30 minutes before switching on the refrigerator.

Is the refrigerator ready to run once it is returned to the upright position or should it rest for a certain period of time before it is turned on?

The positions in which each compressor is allowed to be put are stated in the Product Bulletin – Shipment of Refrigeration Appliances in the Horizontal Position. 

 If the unit has been shipped in the correct position in accordance with the Technical Information, we recommend waiting 30 minutes before switching on the refrigerator.

What is the difference between the standard compressor and the tropical compressor?

There are two main differences between the tropical compressor and the corresponding standard compressor:

  • All tropical compressors can be operated at a maximum ambient temperature of 43°C while most standard compressors are designed to work at temperatures of up to 38°C.
  • While the tropical compressors can be operated at a voltage range from 187 V to 254 V, the corresponding standard compressors have a smaller range of 198 V to 254V.

These factors require the tropical compressors to be equipped with a stronger motor which slightly decreases the COP. 

What do crankcase heaters do and when is the use of a crankcase heater recommended?

The crankcase heater is a heating element which is placed around the compressor to heat the compressor oil during standstill periods.

Depending on temperature and pressure, the oil in the compressor absorbs bigger or smaller amounts of refrigerant. During standstill periods, the oil level in the compressor rises due to the refrigerant solution in the oil. On start-up of the compressor, the pressure on the oil is reduced and the refrigerant dissolves in the form of vapor. This causes the oil to foam. The foam can even reach the compressor suction tube and the cylinder, which can cause the hydraulic pressure in the compressor cylinder. This can result in damaged valves and gaskets.

Especially during the first start and defrost, when the compressor is colder than the evaporator, the oil absorbs a lot of refrigerant. By using a crankcase heater during standstill periods, the compressor can be maintained at a steady temperature so that only a small amount of refrigerant is absorbed by the oil. When starting it for the first time, and in cases where refrigeration systems use a large charge, a crankcase heater must be cut in two to three hours before starting the compressor.There are two cases where a crankcase heater is recommended:

  1. Properly using a crankcase heater can reduce the risk of liquid hammer in cases where the maximum refrigerant charge as given in the compressor's data sheet cannot be complied with. If a crankcase heater is used, the maximum refrigerant charge can be increased by up to 70%.
  2. If the compressor is located where it may get colder than the evaporator, it is always recommended to use a crankcase heater. In the case of extremely low ambient temperatures, oil viscosity can become relatively high. If this causes starting problems, it may be advisable to use a crankcase heater even on domestic appliances.
Is there any Secop compressor suitable for R407C?

Yes there is. Please check our Product Selector for available types.

What determines the noise level of a cooling system?

The most relevant factors are:

  • combination of components in the cooling system (layout and installation)
  • pulsations and turbulences in the refrigerant gas related to the specific system
  • actual level of system insulation
  • f(x) of machine compartment
  • actual system vibration prevention
  • suction and/or pressure mufflers 

Secop's Range of Hermetic Compressors for AC Voltage

Compressor basics e.g., type designation, mounting accessories, country of origin, etc. can be found on our Product Bulletins page.

View all Product Bulletins

Utilizziamo i cookie per personalizzare i contenuti e gli annunci, per fornire funzioni di social media e per analizzare il nostro traffico. Condividiamo inoltre le informazioni sull'utilizzo del nostro sito con i nostri partner di social media, pubblicità e analisi. Cliccate su “Gestione delle preferenze” se volete saperne di più sui nostri cookie e regolare le vostre preferenze. Facendo clic su “Accettare tutti”, si accetta l'uso di tutti i cookie come descritto nella nostra Informativa sulla privacy. Informativa sulla privacy